Model | ALSES 75kWh-150kW | ALSES 300kWh-600kW | ALSES 1MWh-2MW | ALSES 2MWh-4MW |
PV Parameters | ||||
MPPT Voltage Range | DC200V ~ DC700V | |||
MPPT Full Power Volt Range | DC370V ~ DC700V | |||
MPPT Channel Quantity | 0~2 (Optional) | |||
Max Current Per Channel | 135A | |||
AC parameters (On-Grid) | ||||
Rated Output Power | 150kW | 600kW | 2MW | 4MW |
Rated Grid Voltage | 3W+N+PE, 380V/400V | |||
Voltage Range | -15%~+10% | |||
Rated Frequency | 50Hz / 60Hz | |||
Frequency Range | ±2Hz | |||
Output Current Harmonic | ≤3% (Rated Power) | |||
Power Factor | -0.9 ~+0.9 | |||
Overload Capacity | 105%: Continuous Operation; (105% ~ 120%: 10min; 120%); Stop Operation | |||
AC parameters (Off-Grid) | ||||
Rated Output Power | 150kW | 600kW | 2MW | 4MW |
Rated Voltage | 3W+N+PE, 380V/400V | |||
Output Voltage Harmonics | ≤3% (Linear Full Load) | |||
Rated Frequency | 50Hz / 60Hz | |||
Overload Capacity | 105%: Continuous Operation; (105% ~ 120%: 10min; 120%); Stop Operation | |||
Battery | ||||
Battery Type | LFP | |||
Energy of each module | 5.12kWh | |||
Module Qty | 15 | 30 | 45 | 60 |
Total Power | 150kW | 600kW | 2MW | 4MW |
Running Time | 1.5 (optional by Changing Module Qty) | |||
Life Cycle | 4000 Cycles (0.5C@25°C Charging &Discharging @100%DOD, EOL80%) | |||
Protection | ||||
DC Switch | YES | |||
AC Switch | YES | |||
Grid Monitoring | YES | |||
Surge Protection | YES | |||
Basic Parameters | ||||
Dimensions W*D*H | 1680*1502*1700mm | 1680*3788*1700mm | 6058*2438*2591mm | 12,192*2438*2591mm |
Weight | 1395Kg | 5000Kg | 18000Kg | 32000Kg |
Isolation | No | |||
On-Off-Grid Switching | STS | |||
Protection | Outdoor IP54 up IP67 | |||
Working Temperature | -20 ~ 55°C (>45°C Derating) | |||
relative Humidity | 0% RH ~ 95% RH, No Condensation | |||
Cooling | Anodox Adaptive Immersion Thermal Management | |||
Max Working Altitude | 400m (>2000m Derating) | |||
Display | Touch Screen | |||
Communication | RS485, CAN, LAN | |||
Communication Protocol | Modbus-RTU, Modbus-TCP, CAN2.0B | |||